Termination locations, Warning, A. vent termination minimum clearances – Hearth and Home Technologies 8000CF-OAK-IPI User Manual
Page 21
Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. Q • 11/08
21
Figure 6.3 Leveled Termination Caps
A. Vent Termination Minimum Clearances
Roof Pitch
H (Min.) Ft.
Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0
Figure 6.1 Minimum Height From Roof To Lowest Discharge
Opening
* 3 foot minimum in snow regions
HORIZONTAL
OVERHANG
VERTICAL
WALL
GAS DIRECT VENT
TERMINATION CAP
12
X
ROOF PITCH
IS X/ 12
LOWEST
DISCHARGE
OPENING
2 FT.
MIN.
20 INCHES MIN.
H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING
6
6
Termination Locations
Fire Risk.
Maintain vent clearance to combustibles as
specifi ed.
• DO NOT pack air space with insulation or other
materials.
Failure to keep insulation or other materials away
from vent pipe may cause overheating and fi re.
WARNING
DIRECT VENT GAS, WOOD OR FUEL
OIL TERMINATION
A
GAS
TERMINATION
B
C
Gas
Termination
Wood & Fuel Oil
Termination
Comments
A
6 in.
20 in.
Horizontal distance between terminations
B
20 in.
24 in.
Distance to perpendicular wall
C
18 in.
18 in.
Vertical distance between terminations
Minimum Dimensions
DIRECT VENT GAS, WOOD OR FUEL
OIL TERMINATION
20 IN.
(508 MM)
(MINIMUM) TO
PERPENDICULAR
WALL
(GAS ONLY)
WOOD OR
GAS TERMINATION
20 IN. MIN. *
(508 MM)
* IF USING DECORATIVE CAP COVER(S), THIS DISTANCE MAY
NEED TO BE INCREASED. REFER TO THE INSTALLATION
INSTRUCTIONS SUPPLIED WITH THE DECORATIVE CAP COVER.
Figure 6.2 Staggered Termination Caps