beautypg.com

V. removal and replacement of components, Service for refrigerant lines, A] refrigerant recovery – Hoshizaki MODULAR CRESCENT CUBER KM-630MRH User Manual

Page 46: B] evacuation and recharge [r-404a

background image

46

V. REMOVAL AND REPLACEMENT OF COMPONENTS

IMPORTANT

Ensure all components, fasteners and thumbscrews are securely in place after
the equipment is serviced.

IMPORTANT

1. The Polyol Ester (POE) oils used in R-404A units can absorb moisture quickly.

Therefore it is important to prevent moisture from entering the system when
replacing or servicing parts.

2. Always install a new filter drier every time the sealed refrigeration system is

opened.

3. Do not leave the system open for longer than 5 minutes when replacing or
servicing parts.

1. SERVICE FOR REFRIGERANT LINES

[a] REFRIGERANT RECOVERY

The icemaker unit is provided with two Refrigerant Access Valves

one on the low-side and

one on the high-side line. Using proper refrigerant practices recover the refrigerant from
the Access Valves and store it in an approved container. Do not discharge the refrigerant
into the atmosphere.

[b] EVACUATION AND RECHARGE [R-404A]

1) Attach Charging Hoses, a Service Manifold and a Vacuum Pump to the system. Be

sure to connect charging hoses to both High and Low -side Access Valves.

IMPORTANT

The vacuum level and Vacuum Pump may be the same as those for current
refrigerants. However, the rubber hose and gauge manifold to be used for
evacuation and refrigerant charge should be exclusively for POE oils.

2) Turn on the Vacuum Pump. Never allow the oil in the Vacuum Pump to flow backward.

3) Allow the Vacuum Pump to pull down to a 29.9" Hg vacuum. Evacuating period de-

pends on pump capacity.

This manual is related to the following products: