beautypg.com

Installation procedure, Install indoor unit, Warning – haier AE122BCAAA (H2EM-18H03) User Manual

Page 23

background image

!

Permitted length and fall of connecting pipe

Depending on the outdoor units, for details, please refer to the attahed manual of outdoor unit.

Material and dimension of connecting pipe

Perform connection of flared pipe to connect all the refrigerant pipes.

Connection of refrigerant pipe

Two spanners operation

22

Material of connecting pipe

Gas side

Dimension of connecting pipe

(

)

mm

6.35

External diameter of

conneting pipe(mm)

12.7

Installation procedure

Install indoor unit

warning

During installation, if refrigerant leakage occurs, please immediately take ventilation measure.
If the refrigerant gas meet the fire, it may generate poisonous gas.
After finishing installation work, please make sure there is no refrigerant leakage. If the leaked
refrigerant gas meet heater and oven, etc. fire sources, it may generate poisonous gas.

Phospor deoxy copper seamless pipe used in air conditioner (TP )

2

Liquid side

The connection of indoor unit connecting pipe must be performed by

two spanners.

For installation torque, please refer to the following table.

Tightening torque (N.m)

Installation torque (N.m)

6.35

13.7(1.4kgf.m)

11.8(1.2kgf.m)

53.9(5.5kgf.m)

49.05(5.0kgf.m)

12.7