Installation procedure

Install indoor unit

When install the duct hidden type indoor unit, the return air box must be

designed and installed, as Figure 1, Figure 2.

The distance between the air outlet of duct and the air outlet of air

conditioner should be no more than 1m (when the out unit static pressure is 0Pa).

Building roof of installation

Ceiling

Air supply

Air out duct

Unit

Return air

Return air box

(Figure 1)

(Figure 2)

Unit

Return air

Return air box

Air supply

Air ourlet girlle

There should be

no obstacles

M8 wide expansion screw bolt

M8 hoisting screw

M8 wide lock washer

M8 screw nut

A amplified

Unit

(Figure 3)

B Rivet

B amplified

Air supply passage

Air supply passage

Air outlet grille

C amplified

Air supply passage

Use screw to

fix top panel

Top panel of unit

(Figure 4)

Low static pressure duct type: max static pressure is 30Pa.