INSTALLATION

WSK-24 WIRELESS OCCUPANCY SOLUTION

3

62-0300ES—01

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained and experienced service

technician.

WARNING

Risk of electrical shock.
Can cause severe injury, property damage or
death.
Disconnect power supply before installation and
before servicing.

IMPORTANT

The thermostat may be a line voltage powered
device. All wiring must comply with national and
local electrical codes, ordinances and
regulations.

The WSK-24 must be powered by an Approved
24 Vac, Class 2, NEMA rated transformer.

Thermostat Configuration

Refer to the thermostat’s installation instructions for
programming, mounting, and wiring the thermostat.

The receiver has a normally open dry contact relay.
Therefore, the thermostat should be set so that the relay
on the thermostat is normally closed.

Use Table 2 or Table 1 to determine the desired Installer
Codes for the thermostat being used with the WSK-24.

Wiring

Prepare Thermostat for Receiver Wiring

Turn off the thermostat and remove the power source
from the thermostat.

WARNING

Risk of electrical shock.
Can cause severe injury, property damage or
death.
Disconnect power supply before servicing.

CAUTION

Equipment Damage Hazard.
Improper removal can damage the thermostat.
Carefully follow the thermostat removal directions.

Receiver and Thermostat Terminal Wiring

Table 1. MultiPRO™ Installer Setup Codes.

IS

Code

Code

Description

Option

Value

Option Description

0160

Schedule Options 0

Non-Programmable

0340
(Non-
program
mable)

Remote Temp
Sensor/Remote
Setback/
Changeover
Input

5

Remote Setback

0341

Delay for Remote
Setback

0

No Delay

2

Two Minute Delay

0342

Override Option

0

No Override during
unoccupied

1

Override during
unoccupied

0343

Unoccupied
Heating Setpoint

50-65 Range is 50 to 65°F

(10 to 18°C)

0346

Unoccupied
Cooling Setpoint

75-90 Range is 75 to 90°F

(24 to 30°C)

Table 2. SuitePRO™ Installer Setup (IS) Codes.

IS

Code

Code

Description

Option

Value

Option Description

19

Remote
Setback

2

Hotel Card enabled N.C. with
1 second software delay
going from UnOccupied to
Occupied;
2 minute delay going from
Occupied to UnOccupied.

4

Hotel Card enabled N.C. with
1 second software delay
going from UnOccupied to
Occupied;
30 minute delay going from
Occupied to UnOccupied.

20

Remote
Setback for
Heating

50-70 Range is 50 to 70°F

(10 to 21°C)

21

Remote
Setback for
Cooling

72-90 Range is 72 to 90°F

(22 to 32°C)

Table 3. Wiring Designations

Receiver

Harness

Wire

Typical

Thermostat

Terminals

Connection

Red

R

24 Vac Power

White

C

24 Vac Common

White/
Brown

Sc

Dry Contact; Normally
Open

Brown

Sb

Dry Contact; Common