3-phase 5-wire input

Option 6:
3-phase 4-wire input

44 A

44 A

44 A

Required Power Receptacle-
Options 6 and 7

None. Cord, plug and included. Receptacle should be ordered separately. Electrician must
hard wire receptacle to site power.

Maximum Input Power (watts)

8,490

12,196

24,392

Typical Input Power (watts)

5,900
4 cells, 32 GB, 4 I/O chassis
with 6 PCI each

9,800
8 cells, 32 GB, 4 I/O chassis
with 6 PCI each

19,600
16 cells, 32 GB, 4 I/O
chassis with 6 PCI each

Environmental Characteristics

Environmental Characteristics

Environmental Characteristics

Environmental Characteristics

Acoustics

65 dB

Operating temperature

68° to 86°F (20°C to 30°C)

Non-operating temperature

-40° to 158°F (-40° to 70°C)

Maximum rate of temperature
change

68°F/hr (20°C/hr)

Operating relative humidity

15% to 80% @ 86°F (30°C)

Operating altitude

0 to 10,000 ft (0 to 3.1 km)

Non-operating altitude

0 to 15,000 ft (0 to 4.6 km)

Regulatory Compliance

Regulatory Compliance

Regulatory Compliance

Regulatory Compliance

Safety

IEC 950:1991+A1, +A2, +A3, +A4;

EN60950:1992+A1, +A2, +A3, +A4, +A11;

UL 1950, 3rd edition;

cUL CSA C22.2 No. 950 95

Key Dates

Key Dates

Key Dates

Key Dates

First CPL date

6/03

First ship date

3Q03

Dimensions

Dimensions

Dimensions

Dimensions

Height

5.25 ft or 6.43 ft (1.6 meters or 1.96 meters)

Depth

45.5 in (115.67 cm)(same depth as 32W)

Width

24.0 in (60.96 cm)

Electrical Characteristics

Electrical Characteristics

Electrical Characteristics

Electrical Characteristics

AC input power

200-240 VAC, 50/60 Hz

Current requirements at
200V240V

16 A

Typical maximum power
dissipation (watts)

2290

Maximum power dissipation
(watts)

3200

Environmental Characteristics

Same as Superdome

QuickSpecs

HP Integrity Superdome Servers: 16-way, 32-way,

HP Integrity Superdome Servers: 16-way, 32-way,

HP Integrity Superdome Servers: 16-way, 32-way,

HP Integrity Superdome Servers: 16-way, 32-way,

and 64-way

and 64-way

and 64-way

and 64-way

TechSpecs

DA - 11717 Worldwide — Version 2 — July 15, 2003

Page 32

This manual is related to the following products: