beautypg.com

C. vent termination – Heat & Glo Fireplace Heat-n- Glo BE-41 User Manual

Page 21

background image

21

!

C. Vent Termination

For Horizontal Terminations - To attach and secure the

termination to the last section of horizontal vent:
• Rotate and interlock the ends as described at the begin-

ning of the Installing Vent Components section.

• The termination kit should pass through the wall firestops

from the exterior of the building.

• Adjust the termination cap to its final exterior position on

the building.

Figure 24. Round & Trapezoid Termination Caps

!

WARNING: THE BOTTOM OF THE VENT

TERMINATION CAP MUST BE A MINIMUM

OF 12 INCHES (305 MM) ABOVE GROUND LEVEL

(GRADE). THE TOP OF THE CAP MUST BE A MIN-

IMUM OF 18 INCHES (457 MM) BELOW COMBUS-

TIBLE MATERIAL, SUCH AS A DECK. THE SIDE

OF THE CAP MUST BE A MINIMUM OF 6 INCHES

(152 MM) AWAY FROM A PARALLEL OUTSIDE

WALL. VENTING TERMINALS SHALL NOT BE RE-

CESSED INTO A WALL OR SIDING. SEE THE FOL-

LOWING DIAGRAM FOR VENT TERMINATION

CLEARANCES.

ROUND CAP TERMINATION

PERFORATION CANNOT BE

INSIDE THE WALL

7 1/2"

(191mm)

MINIMUM

TRAPEZOID CAP TERMINATION

7 1/4"

(184mm)

WARNING: THE TERMINATION CAP MUST BE PO-

SITIONED SO THAT THE ARROW IS POINTING UP.

For roundcap termination kits:
• Use the exterior pipelock hole on the round flange of the

wall firestop to secure the vent pipe in place.

For trapezoidal cap termination kits:
• Using screws secure the cap to the exterior wall through

the flanges in the cap.

Figure 22. Ceiling Firestop (Ceiling Side)

If the area above the ceiling is NOT an attic, position and

secure the ceiling firestop on the ceiling side of the previously

cut and framed hole.

If the area above the ceiling IS an attic, position and secure

the firestop on top of the previously framed hole.
NOTE: Keep insulation away from the vent pipe at least

1 inch (25mm).

Figure 23. Attic Firestop

JOIST

CEILING FIRESTOP

CEILING

NAILS (4 REQUIRED)

CEILING

CEILING FIRESTOP

RAFTER

NAILS (4 REQUIRED)