2. Continue Adding Vent Components

• Continue adding vent components, locking each succeed-

ing component into place.

• Ensure that each succeeding vent component is secure-

ly fitted and locked into the preceding component in the

vent system.

• 90° elbows may be installed and rotated to any point

around the preceding component’s vertical axis. If an el-

bow does not end up in a locked position with the pre-

ceding component, attach with a minimum of two (2)

sheet metal screws.

3. Install Support Brackets
For Horizontal Runs -
The vent system must be supported

every five (5) feet of horizontal run by a horizontal pipe support.
To install support brackets for horizontal runs:
• Place the pipe supports around the vent pipe.
• Nail the pipe supports to the framing members.

Figure 17. Adding Venting Components

For Vertical Runs - The vent system must be supported

every eight (8) feet (2.4m) above the fireplace flue outlet by

wall brackets.
To install support brackets for vertical runs:
• Attach wall brackets to the vent pipe and secure the wall

bracket to the framing members with nails or screws.

Figure 18. Installing Support Brackets

4. Install Firestops
For Horizontal Runs -
Firestops are REQUIRED on both

sides of a combustible wall through which the vent passes.
NOTE: Model DVK-01TRD does not need an exterior

firestop on an exterior combustible wall.
To install firestops for horizontal runs that pass through

either interior or exterior walls:
• Cut a 12-inch by 12-inch (305mm X 305mm) hole through

the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)

above the center of the horizontal vent pipe.

WALL BRACKET

WALL STUD

1 INCH MIN.

(25.4mm)

8 FT. (2.4m)

FLUE

OUTLET