L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT

®

CONTROLLERS

9

68-0281EFS—06

* Error condition only available when the Outdoor Reset Module is installed.

Table 6. L7224/L7248 Controller Operating Sequence.

Action

System Response

Thermostat calls for heat.

Circulator starts when water temperature is above Low Limit setting (if

applicable) or above the Thermal Purge Temperature Limit (tPL) if

Thermal Purge is enabled. Boiler temperature is checked. Burner

starts when water temperature is below High Limit setting minus the

differential or at or below the Thermal Purge Temperature Limit (tPL)

for cold start boilers if the Thermal Purge Temperature Limit is

enabled. If tPL is enabled, the burner may also start if the boiler

temperature is cooling at 10 ºF or greater per minute or the Thermal

Purge Time Delay (tPt) has expired.

If Anti Short-Cycle Time is enabled, the burner does not start until the

set Anti Short-Cycle Time between cycles expires after the previous

call for heat was satisfied.

Boiler temperature exceeds the High Limit.

Burner is turned off. Burner restarts when the water temperature

drops below the High Limit setting minus the Differential. If Thermal

Purge is enabled, the burner is turned on when either the Thermal

Purge Temperature Limit is reached, the Thermal Purge Time Delay

has expired or the boiler temperature cooling rate exceeds 10 ºF/

minute.

Thermostat is satisfied.

Circulator and burner turn off.

Boiler temperature drops below the Low Limit

setting minus the differential (if applicable).

Burner is turned on, Circulator is turned off. Burner stops when the

water temperature exceeds the Low Limit setting. Power to Zc is

removed.

Error condition

1-5.

If an error condition is detected, all outputs except ZC are shut down.

Burner is off. Control continues to function and restarts when error is

corrected.

During the error check sequence, the system checks for drift in the

sensor and corrosion in the connections.

Error condition 6.

EnviraCOM communication is not available.

Error condition 7.

The control has reset the High Limit, Low Limit and Differential setting to

a default setting and will continue to run at those settings.

Performance of the system will be degraded.

Error condition 8.

If the error condition is detected, all outputs except ZC are shut down.

Burner is off. Control continues to function and restarts when all three

user keys have been pressed longer than 60 seconds.

Error condition 9*.

System continues to run with no outdoor reset functionality

Error condition 10*.

System continues to run with outdoor reset parameters enabled as

programmed. Error cleared automatically.

Error condition 11*.

System continues to run with boiler temp set to High Limit.

Table 7. L7224/L7248 Controller Operating Sequence with multiple zones connected through the ZR terminal.

Action

System Response

Zone Request (ZR) terminal is connected to

L1 (Zone calls for heat).

Boiler temperature is checked. Burner starts when water temperature

is below High Limit setting or at or below the Thermal Purge

Temperature Limit (tPL) for cold start boilers if the Thermal Purge

Temperature Limit is enabled. If tPL is enabled, the burner may also

start if the boiler temperature is cooling at 10 ºF or greater per minute

or the Thermal Purge Time Delay (tPt) has expired. Anti Short-Cycle

Time is applied, see Table 6.

Boiler temperature exceeds the High Limit.

Burner is turned off. Burner restarts when the water temperature

drops below the High Limit setting minus the Differential. If Thermal

Purge is enabled, the burner is turned on when either the Thermal

Purge Temperature Limit is reached, the Thermal Purge Time Delay

has expired or the boiler temperature cooling rate exceeds 10 ºF/

minute.

Zone Request input is de-energized (Zones

are satisfied).

Burner turns off.

Boiler temperature drops below the Low Limit

setting minus the differential (if applicable).

Burner turns on and Zone Control is de-energized. Burner turns off

and Zone Control is re-energized when the water temperature

exceeds the Low Limit setting.