L7224A,C; L7248A,C,L OIL ELECTRONIC AQUASTAT

®

CONTROLLERS

11

68-0281EFS—06

Fig. 9. L7224A,C multizone system with circulator connections.

Boiler is hot,

house is cold.

Display is ON.

120 Vac at C1-C2

120 Vac at C1-C2, check wiring to pump.

Wiring OK, is pump running?

If not, replace the pump.

If pump is running, check for trapped air or

closed zone valves.

Boiler below the Low Limit

temperature, wait for boiler to go

above Low Limit temperature.

Boiler above

LL? If yes, check for

120 Vac between ZC and L2.

If no 120 Vac, replace control.

If yes, check zone relays, circulators and

wiring.

ELL setting (L7248L only)

Set ELL to Off for multizone system (see Fig.

11).

Set ELL to On for External Low Limit (see

Fig. 13).

Boiler above LL? If yes, check 120

Vac at ZR-L2 (only L7248L with

ELL set On)

If no 120 Vac, check C1-C2 (see above).

If yes, check the External Low Limit control.

Boiler is hot,

no hot potable

water.

Display is ON.

Boiler Demand signal from the

water heater (either 120 Vac at

ZR-L2, or 0 Vac on T-T; depends

on installation and “duu” setting)

24 Vac on T-T (or 0 Vac on ZR-L2), check

wiring to water heater

Wiring OK, check the water heater

“duu” setting

Set duu to ON if 120 Vac water heater

demand is connected to ZR

Set duu to OFF if open/closed water heater

demand is connected to T-T

Check DHW Module and DHW

Sensor

DHW Module not properly connected and/or

DHW Sensor improperly positioned

Table 11. Troubleshooting Guide

System

Condition

Diagnostic

Condition

Check

Action

M27115

POWER SUPPLY. PROVIDE DISCONNECT

MEANS AND OVERLOAD

PROTECTION AS REQUIRED.

1

CONTROL CASE MUST BE CONNECTED

TO EARTH GROUND. USE GROUNDING

SCREW PROVIDED.

2

C1

B1

ZC

L2

LINE

C2

ZR

L1

B2

T
T 3

2
1

SENSOR

LINE

VOLTAGE

CIRCULATOR

LINE

VOLTAGE

OIL BURNER

RELAY

2

LOW

VOLTAGE

THERMOSTAT

L7224

3

L1

(HOT)

L2

1

2

1

4

5

6

ZONE 2

LOW VOLTAGE

THERMOSTAT

R845A RELAY ZONE 2

ZONE 2

CIRCULATOR

TO ADDITIONAL R845A

RELAYS FOR OTHER ZONES