8

• Water supply inlet is 1/2" female pipe thread (FPT).
• A minimum of 1/4" nominal ID copper water tubing or equivalent is required for the

icemaker water supply line. An icemaker water supply line shut-off valve and drain valve
must be installed. Be sure there is sufficient extra water supply line for the unit to be
pulled out for service.

• Icemaker drain outlet is 3/4" FPT. A minimum of 3/4" nominal ID hard pipe or equivalent

is required for the icemaker drain line. Be sure there is sufficient extra drain line for the
unit to be pulled out for service.

• Drain line must have 1/4" fall per foot (2 cm per 1 m) on horizontal runs to get good flow.

A vented tee connection is also required for proper flow.

• Drain line should not be piped directly to the sewer system. An air gap of a minimum of

2 vertical inches (5 cm) should be between the end of the drain pipe from the unit and
the floor drain.

Floor

Drain

Fig. 2

Shut-Off
Valve

Drain Valve

Drain Outlet
3/4" FPT

Piping to
approved
drain.

Two-inch
(5 cm) air gap

Water Supply Inlet
1/2" FPT