A. Chimney Requirements

Measure vertical distances from the base of the fi replace
as shown in Figure 8.2.

20 ft (6.10 m) max.
pipe between an
offset & return

Ceiling firestop

35 ft (10.7 m)

max. straight

unsupported

chimney height

16.5 ft (5.03 m) min. height/single offset-return

20 ft. (6.10 m) min. height/double offset-return

90 ft (27.4 m) max. height

6 ft (1.83 m) max.
unsupported chimney
above roof

41-1/4 in.

(1048 mm)

Effective

Height

Figure 8.2 Chimney Requirements

Table 8.1

• Minimum overall straight height

16.5 ft

(5.03 m)

• Minimum height with offset/return

16.5 ft

(5.03 m)

• Maximum height

90 ft

(27.43 m)

• Maximum chimney length between an offset

and return

20 ft

(6.1 m)

• Maximum distance between chimney

stabilizers

35 ft

(10.67 m)

• Double offset/return minimum height

20 ft

(6.1 m)

• Maximum unsupported chimney length

between the offset and return

6 ft

(1.83 m)

• Maximum unsupported chimney height above

the fi replace

35 ft

(10.67 m)

• Maximum unsupported chimney above roof

6 ft

(1.83 m)

WARNING! Risk of Fire! You must maintain 2 in. (51
mm) air space clearance to insulation and other combus-
tible materials around the chimney system. Failure to do
so may cause overheating and fi re.

Determine the chimney components needed to complete
your particular installation:

• Measure the total vertical height of the fireplace

installation from the base of the fi replace assembly to
the approximate location of the bottom of the termination
cap.

• Subtract the effective height of the fi replace assembly

(see Figure 8.2) from the total vertical height to determine
the overall height of the chimney installation.

• Create a schematic for your application similar to Figure

8.2 showing components required (referring to Table
8.1). Figure 8.1 identifi es those components and where
used.

• Install a ceiling fi restop whenever the chimney penetrates

a fl oor/ceiling.

NOTICE:

A maximum of two pairs of offsets and returns

may be used.

CAUTION! Risk of Fire and/or Asphyxiation! DO

NOT connect this fi replace to a chimney fl ue servicing
another appliance. DO NOT connect to any air distribu-
tion duct or system. These actions could cause over-
heating/fi re in the chimney fl ue, or release of exhaust
fumes into the living areas.

Heatilator • A36R & A42R • 28376 • Rev AF • 11/08

HEIGHT OF CHIMNEY COMPONENTS

in.

mm

Chimney Stabilizer

SL3

4-3/4

121

Ceiling Firestops

FS338

0

0

FS339

0

0

FS340

0

0

Offsets/Returns

SL315

13-3/8

340

SL330

15-1/2

394

Roof Flashing

RF370

0

0

RF371

0

0

Chimney Sections*

SL306

4-3/4

121

SL312

10-3/4

273

SL318

16-3/4

425

SL324

22-3/4 578

SL336

34-3/4 883

SL348

46-3/4 1187

* Dimensions refl ect effective height.