Framing & clearances, A. select fireplace location – Hearth and Home Technologies A42R User Manual
Page 18
18
6
6
Framing & Clearances
F
E
D
B
C
Across a
corner
G
As a
room
divider
A
48 in.
(1219 mm)
minimum
B
Along a wall
B
A
5/8 in. (16 mm) all
configurations
G
3/4 in. (19 mm) min. air
space from fireplace to
combustible materials. 1/2
in. (13 mm) allowed at
nailing flanges.
Note:
Note: In addition to these
framing dimensions, also
reference the following
sections:
• Clearances (Section
6.B.)
• Mantel Projections
(Sections 11.E. & 11.F.)
• Fireplace Dimensions
(Section 13.A.)
G
A
In an exterior chase
or projecting into a
garage
B
Note: Measurements are FRAMING dimensions only and do
not include drywall either in the cavity or on the interior walls.
H
H
H
Figure 6.1 Fireplace Locations (Framing dimensions shown)
A. Select Fireplace Location
Model #
A
B
C
D
E
F
G
H
A36
in.
51
43
74 7/8
35 3/4
15 3/4
53
23
12 in. (305 mm)
Minimum from FP
opening to any
perpendicular wall.
mm
1295
1092
1902
908
400
1346
584
A42
in.
57
49
77 1/2
38 7/8
18
54 7/8
23
mm
1448
1245
1969
987
457
1394
584
Heatilator • A36R & A42R • 28376 • Rev AF • 11/08