Ton water/glycol-cooled condensing unit (con't.) – Emerson 3000 User Manual

Page 82

background image

Split System Models

76

Figure 44 5-ton water/glycol-cooled condensing unit (con't.)

DPN000228_Rev0

Field-supplied unit disconnect
switch when factory unit
disconnect switch is not suplied

Electric service;
not by Liebert

WATER/GLYCOL

Optional factory-installed
disconnect switch

Field-supplied 24V
NEC Class 1 wiring
to fan/coil unit

Field-supplied 24V
NEC Class 1 wiring
to drycooler
(glycol-cooled units only)

Line voltage electric
power supply conduit voltage

Removable
Access Panel

Heat rejection connection.
Field-supplied 24V NEC Class 2 wiring.
Wire connections from evaporator mod:
1. 24V ground
2. 24V supply
3. High pressure alarm (optional)
4. Hot gas bypass connection
(only on units with hot gas bypass)

Remote drycooler
connection; field-supplied
24V NEC Class 1 wiring
(glycol-cooled units only)

Connection terminal
for field-supplied
earth grounding wire

Low-voltage electric
power supply conduit
entrance

Field-supplied 24V NEC
Class 1 wiring between
glycol condensing unit
and drycooler

NOTES
1. Refer to specification sheet for full load amp. and wire size amp. ratings.
2. Control voltage wiring must be a minimum of 16 G A (1.6mm) for up to 75' (23m)
or not to exceed 1 volt drop in control line.