Glycol/GLYCOOL-Cooled Models—Self-Contained Compressor

52

Figure 28 General arrangement—GLYCOOL models with digital scroll compressor

r

Digital
Solenoid
Valve

Pump
Housing

Glycol

Pump

Unions*

Isolation
Valves*

Expansion
Valve

Evaporator
Coil

Drycooler
Coil

Drycooler
Electric
Box

Unions*

Pressure
Port*

Hose
Bib*

Fill*

Fluid
Return to
Pump

Fluid
Supply
from
Pump

Air Vents*
at Top of
Risers

Flow Regulating Valve*

Pressure
Port*

Sight
Glass

Sensing
Bulb

External
Equalizer

Service
Valves

Filter
Dryer

Econ-O-Coil

3-Way Chilled
Glycol Valve

3-Way Motorized
Ball Valve

Valve
Actuator

Econ-O-Cycle
Comparator

Econ-O-Coil
Circuit

Tube
in Tube
Condenser

Fluid
Supply to
Unit

Fluid
Return
from
Unit

Isolation
Valves*

Hose
Bibs*

FACTORY PIPING

FIELD PIPING

*Components are not supplied by Liebert but
are recommended for proper circuit operation
and maintenance.

Expansion Tank Field-Installed at
Highest Point in System

DPN001724
Rev. 0

Field-Supplied
Reducers
Required on 3-Ton Units

To iCOM Control

Digital
Compressor