Water-Cooled Models—Self-Contained Compressor

40

4.4.2 Adjustment

Both pressure thresholds can be shifted simultaneously over a 50psi (345kPa) range (the 35psi

[241kPa] differential remains constant). The ball valve setpoint offset parameter in the Liebert iCOM

Service menu can be adjusted from 0 to 50 PSI (345 kPa) to raise or lower the control band similar to

the pressure adjustment on a water regulating valve. Changing the setpoint offset will adjust the

pressure thresholds for both circuits. Units are factory-set at a 30psi (207 kPa) setpoint offset (30psi

[207 kPa] above minimum). This results in a 220psiA (1517kPa) lower threshold and a 255psiA

(1758kPa) upper threshold pressure.

4.4.3 Startup

The setpoint offset is adjusted to the minimum value during startup, then changes to the set value

once the compressor reaches normal operating pressures. Changes in fluid temperature could cause

pressure changes that do not result in valve movement within the deadband. Fan cycling stats should

be set to prevent continuous fluid temperature swings greater than 10

°

F (5.6

°

C).

4.4.4 Location

The motorized ball valve is located in the condenser fluid return line. Three-way valves are piped in a

mixing arrangement with the common port at the valve outlet.

4.4.5 Manual Control

The valve can be manually set by disconnecting AC power, depressing the manual override button on

the valve actuator and adjusting the valve position with the handle. The motorized ball also can be

controlled through the Liebert iCOM’s Service menu using manual mode to override the normal con-

trol.