Table 21 unit refrigerant charge, Table 21, Unit refrigerant charge – Emerson 3000 User Manual

Page 64: Table 22, Table 23

background image

Split System Models

58

Refrigerant charge requirements: Total refrigerant charge will be required only if units are evacuated

during installation or maintenance. Total refrigerant charge = evaporator + lines + condensing unit.

Once all piping is complete, check for leaks and dehydrate the field piping as follows:
1. Pressurize the field piping to 150 PSIG (1034 kPa) using dry nitrogen with a trace of refrigerant.

Check system for leaks with a suitable leak detector.

2. After completion of leak testing, release the test pressure (per local code) and pull a deep vacuum

on the field piping with a suitable pump.

3. After 15 minutes, check the pressure readings and, if they have not changed, break vacuum with

dry nitrogen. Pull a second vacuum to 250 microns or less. Recheck the pressure after 15 minutes.

NOTE
All condensing units and 3-ton evaporator units are fully charged with refrigerant. All 5 ton

evaporator units include a nitrogen holding charge only. See Table 21 for field charge

required. If field-supplied refrigerant piping is installed, refrigerant must be added to the

system.

Table 21

Unit refrigerant charge

Model

R407C Charge

Model

R407C Charge

lb (kg)

lb (kg)

BF/BU 036E

0.5 (0.2)

PF_042A-_H

25.8 (11.7)

BF/BU 035E

0.5 (0.2)

PF_041A-_H

25.8 (11.7)

BF/BU 060E

0.8 (0.4)

PF_067A-_L

25.8 (11.7)

BF/BU 059E

0.8 (0.4)

PF_066A-_L

25.8 (11.7)

MC_40/39A

12.9 (5.8)

PF_Z67A-_L

50.1 (22.7)

MC_65/64A

26.1 (11.8)

PF_Z66A-_L

50.1 (22.7)

PF_042A-_L

12.9 (5.8)

PF_067A-_H

50.1 (22.7)

PF_041A-_L

12.9 (5.8)

PF_066A-_H

50.1 (22.7)

PF_Z42A-_L

25.8 (11.7)

MC_44/43W

3.4 (1.5)

PF_Z41A-_L

25.8 (11.7)

MC_69/68W

5.9 (2.7)

Table 22

Line charges - refrigerant per 100 ft. (30 m) of Type “L” copper tube

O.D.

R407C

Liquid Line

lb (kg)

Suction Line

lb (kg)

1/2"

7.3 (3.3)

-

5/8"

11.7 (5.3)

0.4 (0.2)

7/8"

24.4 (11.1)

1.0 (0.4)

1-1/8"

41.6 (18.9)

1.7 (0.7)

1-3/8"

63.3 (28.7)

2.7 (1.1)

Table 23

Recommended refrigerant lines (R407C) sizes OD copper

Equivalent Feet (m)

3.5-Ton

036E (035E)

5-Ton

060E (059E)

Suction

Liquid

Suction

Liquid

0-50 (0-15)

7/8"

1/2"

1-1/8"

1/2"

51-100 (16-30)

1-1/8"

1/2"

1-1/8"

5/8"

101-150 (31-45)

1-1/8"

5/8"

1-3/8"

5/8"