Setting and using method

Installation Manual

15

ENGLISH

5) Compressor stop mode

Ú

Compressor stop mode: The compressor is stopped during cool/heat operation.

Ú

Power save mode: Adjust the set temperature to +3°C for cooling and -3°C for heating.

6) Operating mode selection mode

Input A Input B Operating mode

OFF OFF

ON OFF

OFF ON

ON ON

Indoor unit operating (Compressor in stop mode), locked

Indoor unit prior operating condition maintained

(Compressor not in stop mode), unlocked

Indoor unit stopped, locked

Indoor unit stopped, locked

CONTROL_

MODE S/W

B

7) Compressor stop mode when interlocking with Economizer

Ú

When interlocking with Economizer, turn On 2nd switch of SETTING.

Input A Input B Operating mode

OFF OFF

ON OFF

OFF ON

ON ON

OFF OFF

ON OFF

OFF ON

ON ON

Indoor unit stopped, unlocked

Indoor unit in cool/high operation, unlocked

Indoor unit in heat/high operation, unlocked

Indoor unit in fan/high operation, unlocked

Indoor unit stopped, locked

Indoor unit in cool/high operation, locked

Indoor unit in heat/high operation, locked

Indoor unit in fan/high operation, locked

CONTROL_

MODE S/W

C

D

Input A Input B Operating mode

OFF OFF

ON OFF

OFF ON

ON ON

Indoor unit prior operating condition maintained

(Compressor not in stop mode), unlocked

Indoor unit operating (Compressor in stop mode), unlocked

Indoor unit stopped, unlocked

Indoor unit stopped, unlocked

CONTROL_

MODE S/W

E