Dry Contact for setback

3) Fan level setting mode

4) Power save mode

Ú

When the indoor unit is operating with a Dry Contact For Setback, the fan level can be changed by other
controller when the fan level is set to low level and the indoor is in unlocked condition.

Ú

When setting 9, A mode, the TEMP_SETTING must always be set to ON.

Ú

Power save mode: Adjust the set temperature to +3°C for cooling and -3°C for heating.

Input A Input B Operating mode

OFF OFF

ON OFF

OFF ON

ON ON

OFF OFF

ON OFF

OFF ON

ON ON

Indoor unit operating at low level, locked

Indoor unit operating at low level, unlocked

Indoor unit stopped, locked

Indoor unit stopped, locked

Indoor unit operating at low level, locked

Indoor unit operating at low level, unlocked

Indoor unit stopped, locked

Indoor unit prior operating condition maintained, unlocked

CONTROL_

MODE S/W

7

8

Input A Input B Operating mode

OFF OFF

ON OFF

OFF ON

ON ON

OFF OFF

ON OFF

OFF ON

ON ON

Indoor unit operating in power save mode, locked

Indoor unit operating in power save mode, unlocked

Indoor unit stopped, locked

Indoor unit operating not in power save mode, unlocked

Indoor unit operating in power save mode, locked

Indoor unit operating in power save mode, unlocked

Indoor unit stopped, locked

Indoor unit stopped, locked

CONTROL_

MODE S/W

9

A