Gas line connection, Initial installation, Never use an open flame for leak testing – Enviro C-10637 User Manual

Page 16: Qualified installers only g

background image

Initial Installation

QUALIFIED INSTALLERS ONLY

G

AS

L

INE

C

ONNECTION

:

Warning: Only persons licensed to work with gas piping may make the necessary gas connections to

this appliance.

Gas Line Connection:
•This fireplace is equipped with a certified flexible pipe located on the right side of the unit, terminating

in a 3⁄8” male NPT fitting. Consult the local authorities for local codes or use the CAN/CGA B149 (1 or 2)

installation code in Canada. In the US, gas installations follow either local codes or the current edition of

the National Fuel Gas Code ANSI Z223.1.
•The efficiency of this unit is a product thermal efficiency rating determined under continuous operating

conditions and was determined independently of any installed system.

The appliance and its’ shut-off valves must be

disconnected from the gas supply piping system

during any pressure testing where the pressure

exceeds 1⁄2 psig (3.45 KPa) or the valve will be

damaged.
The unit must be isolated from the gas supply

piping system by closing its’ individual manual

shut off valve during any pressure testing of the

gas supply piping system at pressures equal to

or less than 1⁄2 psig (3.45 KPa).

Always check for gas leaks with a soap and

water solution after completing the required

pressure test.

O

L I

T

P

TP

TH

TP

TH

IN

OU

T

H

I

LO

N

OF

O

F

LI

P

T O

��������

�������� ���

�����

�������� ���

������

����

����� ����������

�����

��� �������

����

Main Burner

Natural Gas

Propane Gas

Orifice:

#32 DMS

#49 DMS

Venturi Setting:

1⁄2” Min.

7⁄8” Min.

Manifold Press:

3.8 W.C. (0.95 KPa) 11.0 W.C. (2.74 KPa)

Min. Manifold Press: 1.2 W.C. (0.30 KPa) 2.7 W.C. (0.67 KPa)
Max. Supply Press:

7.0 W.C. (1.74 KPa) 13.0 W.C. (3.28 KPa)

Min. Supply Press:

5.0 W.C. (1.24 KPa) 12.0 W.C. (2.98 KPa)

Max. Input:

41,000 BTU/hr

(12.0 KW)

41,000 BTU/hr

(12.0 KW)

Min. Input:

23,000 BTU/hr

(6.7 KW)

21,000 BTU/hr

(6.1 KW)

TO TEST VALVE PRESSURES:

The pressure taps are located on the top right

of the valve.
• Turn set screw one (1) turn counter-clockwise

to loosen.

• Place

5

/

16

in (8 mm) I.D. hose over the

pressure taps.

• Check pressures using a manometer.
• When finished, release pressure, remove

hose and tighten set screw.

NEVER USE AN OPEN FLAME FOR LEAK TESTING.

Figure 15: Fully labeled gas valve.

Table 4: Orifice and Pressure Information.

16