Initial Installation
QUALIFIED INSTALLERS ONLY
E
LECTRICAL
R
EQUIREMENTS
:
Fan Control
Black
White
White
Black
Green/Yellow
Green
Black
Power Cord
120V AC
FAN
120
o
F (49
o
C)
Temperature Sensor
CNT2
CNT3
CNT1
CNT4
The fan is thermostatically controlled and it will
not operate if the appliance is cold. A few minutes
after the appliance is lit and the variable speed
control is set at a desired setting, the fan will
automatically turn on. The fan will automatically
turn off after the appliance has cooled down.
The fireplace must be electrically connected and
grounded in accordance with local codes or, in the
absence of local codes, with the current CSA C22.1
Canadian Electrical Code Part 1, Safety Standards
For Electrical Installations, or The National
Electrical Code ANSI / NFPA 70 in the US.
WARNING: The electrical grounding instructions
must be followed. The fan kit is equipped with a
three-prong (grounding) plug for your protection
against shock hazard, and should be plugged
directly into a properly grounded three-prong
outlet. DO NOT cut or remove the grounding
prong from this plug.
Wire Size
Max. Length
14 gauge
100 ft (30.48 m)
16 gauge
60 ft (18.29 m)
18 gauge
40 ft (12.00 m)
20 gauge
25 ft (7.62 m)
22 gauge
18 ft (5.49 m)
COOL / HEAT
PROGRAM
DOWN
UP
70 ° F
70 ° F
ON
OF
F
Optional
Remote
Control
Purple
Grey
Optional
Wall Switch
Optional
Thermostat
Pilot
Adjustment
Screw
ON/OFF/REMOTE
Thermostat Switch
Blue
Thermopile
Thermocouple
Manifold
Pressure
Tap
Inlet
Pressure
Tap
Gas
Control
Valve
Blue
BV Only
300
o
F (149
o
C)
Temperature
Sensor
(DV has only
connectors)
Figure 14: Wiring of a valve and thermostat.
Table 3. Recommended Thermostat
Wire Size.
Figure 13: Fan wiring diagram.
CAUTION: When servicing controls,
label all wires prior to disconnection.
Wiring errors can cause improper
and dangerous operation. Verify
proper operation after servicing.