beautypg.com

4) interface specifications, 5) clock and backup memory specifications, 1 specifications – Epson FEH300b User Manual

Page 17

background image

2-3

2-1 Specifications

(4) Interface specifications

Item

Specifications

D-sub 9-pin (CN1)

Applicable
standards

RS-232C, RS-422/485

Synchronization

Asynchronous type

Data length

7- or 8-bit

Parity

None, odd, even

Stop bit

1- or 2-bit

Baud rate

4800, 9600, 19200, 38400, 57600, 76800, 115.2kbps
(187500 bps for MPI connection

(Note))

Applications

PLC, temperature controller, barcode reader, etc.

Modular jack 8-pin
(MJ1/MJ2)

Applicable
standards

RS-232C, RS-485 (2-wire connection)

Applications

Screen data transfer (MJ1), PLC, temperature controller, CREC, barcode reader,
V-I/O, Multi-link 2, V-Link, etc.

USB connector
(USB-A/B)

Applicable
standards

Compliant with USB version 1.1

Baud rate

Low speed: 1.5 Mbps, full speed: 12 Mbps

Applications Printer (EPSON PM series), CF card reader/writer

Applicable
standards

Compliant with USB version 1.1

Baud rate

Low speed: 1.5 Mbps, full speed: 12 Mbps

Applications Screen data transfer, PictBridge-compatible printer

Ethernet port
100BASE-TX/
10BASE-T
(LAN)

Applicable
standards

Compliant with IEEE802.3u (100BASE-TX), IEEE802.3 (10BASE-T)

Baud rate

100 Mbps, 10 Mbps

Recommended
cable

100

UTP (unshielded twist-pair cable), category 5, max. 100 m long

Applications

PLC connection, etc.

CF card interface

Compliant with CompactFlash

TM

Extensional communication port
(CN5)

Controller unit connection
(The communication unit is not connectable.)

Optional unit port (CN7)

RGB input/output, video, sound
(The optional unit "GU-xx" is necessary.)

Note) For details, refer to the User’s Manual (2201NEx).

(5) Clock and backup memory specifications

Item

Specifications

Battery specification

Coin-type lithium primary cell

Backup memory

SRAM 512 kbytes

Backup period

Approx. 5 years (Ambient temperature at 25 °C)

Battery voltage drop detection

Provided (Internal memory of $s167 allocated)

Calendar accuracy

Monthly deviation ±90 s (Ambient temperature at 25 °C)

(Note)

Note) Time loss is approximately 90 seconds a month in an ambient temperature of 25

°

C in the non-energized state

(backup with battery). Depending on the ambient temperature, the calendar may lose 356 seconds or advance
189 seconds in a month at the maximum. Correct the clock periodically.