Electrical requirements, Initial installation, Qualified installers only e – Enviro C-11212 User Manual
Page 18
18
Initial Installation
QUALIFIED INSTALLERS ONLY
E
LECTRICAL
R
EQUIREMENTS
:
The fan is thermostatically controlled and
it will not operate if the appliance is cold.
A few minutes after the appliance is lit and
the variable speed control is set at a desired
setting, the fan will automatically turn on.
The fan will automatically turn off after the
appliance has cooled down.
The fireplace must be electrically grounded
in accordance with local codes or, in the
absence of local codes, with the current
Canadian Electrical Code CSA C22.1, or The
National Electrical Code ANSI / NFPA 70 in
the US. This appliance must be connected
to a line-voltage electrical supply.
WARNING: The electrical grounding
instructions must be followed. The fan kit
is equipped with a three-prong (grounding)
plug for your protection against shock
hazard, and should be plugged directly into
a properly grounded three-prong outlet. DO
NOT cut or remove the grounding prong
from this plug.
COOL / HEAT
PROGRAM
DOWN
UP
70 ° F
70 ° F
ON
OF
F
Optional
Remote
Control
Purple
Grey
Optional
Wall Switch
Optional
Thermostat
Pilot
Adjustment
Screw
ON/OFF/REMOTE
Thermostat Switch
Blue
Thermopile
Thermocouple
Manifold
Pressure
Tap
Inlet
Pressure
Tap
Gas
Control
Valve
Blue
BV Only
300
o
F (149
o
C)
Temperature
Sensor
(DV has only
connectors)
Figure 23: Wiring of a valve and thermostat.
Table 4. Recommended Thermostat
Wire Size.
Wire Size
Max. Length
14 gauge
100 ft (30.48 m)
16 gauge
60 ft (18.29 m)
18 gauge
40 ft (12.00 m)
20 gauge
25 ft (7.62 m)
22 gauge
18 ft (5.49 m)
Figure 22: Fan wiring diagram.
CAUTION: Label all wires prior
to disconnecting when servicing
controls. Wiring errors can cause
improper and dangerous operation.
Verify proper operation after
servicing.