Sending the configuration to an-x – ProSoft Technology AN-X-AMX User Manual
Page 37

AN-X-DCSNet2 Page
33
,ConnStats15
Sample File – DCS Master
The following sample file shows how data is mapped for an AN-X
configured as a DCS master.
ClxName,DCSmaster
ClxPrefix,DCSmaster2
ClxSlot, 0
DataOutput
,0,32,8
,1,32,32
,2,32,32
DataInput
,1,0,32
,2,0,32
ClxSlot, 15
DataOutput
DataInput
,0,0,32
,ConnStats0
,ConnStats15
Sending the Configuration to AN-X
When the configuration is complete, save it to a file. If you are using a
spreadsheet to create the configuration, save it as a file of type comma
separated variable (CSV).
To send the configuration to the AN-X:
1. Start your web browser
2. Enter the AN-X IP address as the address, for example, 192.168.0.10
3. Select Automation Network/Configure ControlLogix Support
4. Browse or type in the configuration file name
5. Click Send To AN-X
The web interface displays the result of the upload, either success or an
error message. To see further details, select Log Files/ControlLogix Log
(see page 54) and check for error messages.