MVI46-MCM Database Definition
This section contains a listing of the internal database of the MVI46-MCM
module. This information can be used to interface other devices to the data
contained in the module.
Register Range
Modbus Low
Modbus High
Content
Size
0 to 4999
40001
45000
User Data
5000
5000 to 5009
45001
45010
Backplane Configuration
10
5010 to 5039
45011
45040
Port 1 Setup
30
5040 to 5069
45041
45070
Port 2 Setup
30
5200 to 6199
45071
46070
Port 1 Commands
1000
6200 to 7199
46071
47070
Port 2 Commands
1000
7200 to 7232
47201
47233
Misc. Status Data
33
7600 to 7799
47601
48000
Command Control
200
The User Data area holds data collected from other nodes on the network
(master read commands) or data received from the processor (write blocks).
Additionally, this data area is used as a data source for the processor (read
blocks) or other nodes on the network (write commands).