ProSoft Technology MVI46-MCM User Manual
Page 19

MVI46-MCM ♦ SLC Platform
Configuring the MVI46-MCM Module
Modbus Communication Module
User Manual
ProSoft Technology, Inc.
Page 19 of 108
March 29, 2011
File M0
Offset
Register
Content
Description
N10:16
17
5016
Baud Rate
This is the baud rate to be used on the port. Enter
the baud rate as a value. For example, to select
19K baud, enter 19200. Exceptions: 38400 baud,
enter 384. 57600 enter 576. 115000 enter 115.
N10:17
18
5017
Parity
This is the parity code to be used on the port. The
coded values are as follows:
0=None
1=Odd
2=Even
N10:18
19
5018
Data Bits
This parameter sets the number of data bits for
each word used by the protocol. Enter a value in
the range of 5 to 8.
N10:19
20
5019
Stop Bits
This parameter sets the number of stop bits for
each data value sent. Enter a value of 1 or 2.
N10:20
21
5020
RTS On Delay
This parameter sets the number of milliseconds to
delay after RTS is asserted before the data will be
transmitted. Enter a value in the range of 0 to
65535.
N10:21
22
5021
RTS Off Delay
This parameter sets the number of milliseconds to
delay after the last byte of data is sent before the
RTS modem signal will be set low. Enter a value in
the range of 0 to 65535.
N10:22 23
5022
Minimum
Response
Delay
This parameter sets the number of milliseconds to
wait before a response message is sent out of the
port. This parameter is required when interfacing to
a slow responding device. Enter a value in the
range of 0 to 65535.
N10:23
24
5023
Use CTS Line
This parameter specifies if the CTS modem control
line is to be used. If the parameter is set to 0, the
CTS line will not be monitored. If the parameter is
set to 1, the CTS line will be monitored and must be
high before the module will send data. Normally,
this parameter is required when half-duplex
modems are used for communication (2-wire).
N10:24
25
5024
Slave ID
This parameter defines the virtual Modbus slave
address for the internal database. Any requests
received by the port with this address will be
processed by the module. Verify that each device
has a unique address on the network.
N10:25
26
5025
Bit Input Offset
This parameter specifies the offset address in the
internal Modbus database for network requests for
Modbus function 2 commands. For example, if the
value is set to 150, an address request of 0 will
return the value at register 150 in the database.
N10:26
27
5026
Word Input Offset
This parameter specifies the offset address in the
internal Modbus database for network requests for
Modbus function 4 commands. For example, if the
value is set to 150, an address request of 0 will
return the value at register 150 in the database.