ProSoft Technology MVI46-MCM User Manual
Page 68

Reference MVI46-MCM
♦ SLC Platform
User Manual
Modbus Communication Module
Page 68 of 108
ProSoft Technology, Inc.
March 29, 2011
Block Request from Processor to Module
M1 Offset
Description
Length
7800
3000 or 3100
1
7801
Number of Slaves in Block
1
7802 to 7927
Slave Indexes
126
The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block.
Block Response from Module to Processor
M0 Offset
Description
Length
0
3000 or 3100
1
1
Number of Slaves Processed
1
Ladder logic can be written to override the value in the slave status table to
enable the slave (state value of 1) by sending a special block. Port 1 slaves are
enabled using block 3001, and Port 2 slaves are enabled using block 3101. Each
block contains the slave node addresses to enable.
Block Request from Processor to Module
M1 Offset
Description
Length
7800
3001 or 3101
1
7801
Number of Slaves in Block
1
7802 to 7927
Slave Indexes
126
The module will respond with a block with the same identification code received
and indicate the number of slaves acted on with the block.
Block Response from Module to Processor
M0 Offset
Description
Length
0
3001 or 3101
1
1
Number of Slaves Processed
1