Port 1 Commands
File M0
Offset
Register
Content Description
N11:0 to
N11:09
71 to 80
5200 to 5209 Command #1
This set of registers contains the parameters for the
first command in the master command list. Refer to
the data object section of the documentation.
N11:10 to
N11:19
81 to 90
5210 to 5219 Command #2
Command #2 dataset
1061 to 1070 6190 to 6199 Command #100
Command #100 dataset
Port 2 Commands
File M0
Offset
Register Content
Description
N12:0 to
N12:09
1071 to 1080 6200 to 6209
Command #1
This set of registers contains the parameters for the
first command in the master command list. Refer to
the data object section of the documentation.
N12:10 to
N12:19
1081 to 1090 6210 to 6219
Command #2
Command #2 dataset
2061 to 2070 7190 to 7199
Command #100
Command #100 dataset
Command Control
Register Content
Description
7800
Command Code
Enter one of the valid control command codes in this register to control the
module (9997, 9998, or 9999). Refer to Command Control (page 69, page 25,
page 64) for more information.
7801 to 7999 Command Data
Reserved for future use.