ProSoft Technology MVI69L-MBS User Manual
Page 84

Using Controller Tags
MVI69L-MBS ♦ CompactLogix Platform
User Manual
Communication Module
Page 84 of 154
ProSoft Technology, Inc.
January 6, 2014
5.4.3.3 MBS.CONTROL.EventCmd_DBData
This array allows the processor to dynamically build Modbus commands (for
periodic use) with data associated to the MBS database.
Tag Name
Range
Description
MBS.CONTROL.EventCmd_DBData.
EventCmdTrigger
0 or 1
Toggle to send Event Command.
0 = Disable, 1 = Enable
MBS.CONTROL.EventCmd_DBData.
PortNumber
1
Port number to be associated with
command Control function
MBS.CONTROL.EventCmd_DBData.
SlaveID
1 to 248
Slave ID of Modbus slave
MBS.CONTROL.EventCmd_DBData.
InternalDBAddress
0 to 479 or
0 to 3839
(bit-level)
Used only if UseModuleDBAddress=1.
Allowable range is 0 to 479 for Modbus
Function Codes 3, 4, 6, or 16, and 0 to
3839 for Function Codes 1, 2, 5, or 15.
MBS.CONTROL.EventCmd_DBData.
PointCount
0 to 125
Number of bit/words associated with this
command.
MBS.CONTROL.EventCmd_DBData.
SwapCode
0 to 3
Swap code 0 = no swap, 1 = word swap, 2
= words & byte swap, 3 = byte swap
MBS.CONTROL.EventCmd_DBData.
ModbusFunctionCode
-
Modbus function code (1,2,3,4,5,6,15,or
16)
MBS.CONTROL.EventCmd_DBData.
DeviceDBAddress
0 to 9999
Modbus address of the target slave
database
MBS.CONTROL.EventCmd_DBData.
EventCmdStatusReturned
-
Event status returned by the module
5.4.3.4 MBS.CONTROL.EventCmd_ProcessorData
This array allows the processor to dynamically build Modbus commands (for
periodic use) with processor data.
Tag Name
Range
Description
MBS.CONTROL.EventCmd_ProcessorData.
CmdTrigger
0 or 1
Toggle to send Event Command.
0 = Disable, 1 = Enable
MBS.CONTROL.EventCmd_ProcessorData.
GetStatusTrigger
0 or 1
Toggle to retrieve event status.
0 = Disable, 1 = Enable
MBS.CONTROL.EventCmd_ProcessorData.
PortNumber
1
Port number to be associated with
command
MBS.CONTROL.EventCmd_ProcessorData.
SlaveAddress
1 to 248
Slave ID of Modbus slave
MBS.CONTROL.EventCmd_ProcessorData.
ModbusFunctionCode
-
Modbus function code (5,6,15,or 16)
MBS.CONTROL.EventCmd_ProcessorData.
DeviceDBAddress
0 to
9999
Modbus address of the target slave
database
MBS.CONTROL.EventCmd_ProcessorData.
PointCount
0 to 125
Number of bit/words associated with
this command.
MBS.CONTROL.EventCmd_ProcessorData.
Data[x]
0 to 49
Data values to be sent to the slave
MBS.CONTROL.EventCmd_ProcessorData.
EventCmdStatusReturned
-
Command status
MBS.CONTROL.EventCmd_ProcessorData.
Port1Status
-
Port 1 Status array
MBS.CONTROL.EventCmd_ProcessorData.
Port1Status.Status
-
Status code (Check error code listings
on page 101)
MBS.CONTROL.EventCmd_ProcessorData.
Port1Status.LastError
-
Last error code