MVI69L-MBS ♦ CompactLogix Platform

MVI69L-MBS Configuration

Communication Module

User Manual

ProSoft Technology, Inc.

Page 51 of 154

January 6, 2014

3.2

Module Configuration Parameters

3.2.1 Module

This section contains general module configuration parameters. The module
uses 240 words of read data (user input data) and 240 words of write data (user
output data).

Parameter

Value

Description

Module Name

ASCII
characters
(max. 80)

Assigns a name to the module that can be viewed using
the configuration/debug port. Use this parameter to
identify the module and the configuration file.

Backplane Fail Count

0 to 65535

Specifies the number of consecutive backplane transfer
failures that can occur before communications should be
halted.

Error/Status Block
Pointer

-1 to 239

Starting register location in

the module’s database for the

error/status table. If a value of -1 is entered, the
error/status data is not placed in the database. All other
valid values determine the starting location of the data.
This data should be placed within the read data range of
module memory.

This data area includes the module version information
and all server error/status data. Refer to MBS.STATUS on
page 87 for more information.

Initialize Input Image

Yes or No

This parameter is used to determine if the input image
data, the module’s Read Register Data values, should be
initialized with Read Register Data values from the
processor. If the value is set to No, the Read Register
Data values in the module is set to 0 upon initialization. If
the value is set to Yes, the data is initialized with Read
Register Data values from the processor. Using this option
requires associated ladder logic to pass the data from the
processor to the module.

Slot Number

1 to x

Represents the slot in the CompactLogix rack where the
module resides.