beautypg.com

Installation, Input connections, Load connections – KEPCO KLP Series Quick Start Guide, P/N 228-1616, Rev 2 User Manual

Page 5: Input connections load connections

background image

102607

228-1616 REV 2

5

KEPCO, INC. " 131-38 SANFORD AVENUE " FLUSHING, NY. 11355 U.S.A. " TEL (718) 461-7000 " FAX (718) 767-1102

http://www.kepcopower.com " email: [email protected]

INSTALLATION.

Install units in a 19 inch-wide rack. Optional slides may be used. Leave the front

and rear panels clear of obstructions to ensure adequate cooling. For parallel, series and master-slave
configurations, refer to the User Manual.

INPUT CONNECTIONS. Wire the mating source power connector provided (142-0381) for your input
mains (see Table 5 for mains voltage range). The user must provide a properly sized and rated mains
lead (line cord) and service with a current rating compatible with the anticipated input current. Line cords
available as accessories are listed in Table 3. Plug the source power connector into the source power
inlet connector at the rear panel.

LOAD CONNECTIONS. Connect the load to the (+) and (–) DC OUTPUT terminals on the rear panel
(Figure 2). (+M) and (–M) outputs are for connection of external monitoring equipment such as a DVM,
oscilloscope, etc.

Configuration of local sensing is facilitated by pre-installed jumpers which configure the unit for local
sensing.as shown in Figure 2.

NOTE: Output Sense lines must be connected for proper operation, either locally, or at the load

(remote).

FIGURE 1. KLP SERIES, FRONT PANEL CONTROLS AND INDICATORS

TABLE 5. INPUT CURRENT SERVICE RATING AND CONDUCTOR SIZES

MAINS VOLTAGE RANGE

CURRENT SERVICE RATING

CONDUCTOR SIZE

100 - 132V a-c, 50/60Hz

20 Amp

#12AWG [2,0 mm²]

180 - 265V a-c, 50/60Hz

15 Amp

#14AWG [3,0 mm²]

POWER ON/OFF

Turns unit on/off.

Circuit Breaker

gives input

protection.

VOLTAGE

control/momentary

switch

Rotate to set

output voltage.

Tap to enter

SETPOINT mode.

(Also used for

other functions.)

DC VOLTS

Display shows

output voltage or

voltage setpoint.

(Also used for

special functions).

CV

indicator lights

green when
operating in

constant voltage

mode

Status

Display normally

blank. Shows

active function or

blinks for error

messages.

CC

indicator lights

amber when

operating in

constant current

mode

DC AMPERES

display shows

actual output

current or

current set point

(Also used for

special functions.)

CURRENT

control/momentary

switch

Rotate to set

output current.

Tap to enter

SETPOINT mode.

(Also used for

other functions.)

DC OUTPUT

indicator lights

green to show

output enabled

DC OUTPUT

on/off switch

enables or

disables output.

(Also used to

accept front panel

inputs.)

PROTECT

momentary switch

Used to set

overvoltage and

overcurrent

protection limits.

Requires a thin

tool (e.g., end of

paper clip) to
press switch.

LAN

indicator

lights green

when LAN

interface is

in use

[-1.2K Models]

FUNCTION

momentary switch

Used to access

calibration,

GPIB address,

RS232 baud rate

(-1200 Models),

Virtual Model and

Utility functions.

Requires a thin

tool (e.g., end of

paper clip) to
press switch.