2 link selection, 3 pushbutton and switches, 4 terminals – SAF OPAL SS6 User Manual

Page 21: 1 customer terminals, Link selection, Pushbutton and switches, Terminals, Customer terminals

background image

OPAL SS6 Reduced Voltage Starters

Page 14

3.3.2 LINK SELECTION

LINK

NAME

POSITION

DESCRIPTION

JP1

DUTY

NO

JUMPER

With no jumper present, heavy duty mode
selected
Shipped from factory with no jumper

JP3

RATE

OFF

Selects constant current mode
RV1 has no bearing

ON

This selects current ramp mode which is
dependent on RV1

*Note : JP2 does not exist on this version

3.3.3 PUSHBUTTON AND SWITCHES

SWITCH

NAME

DESCRIPTION

SW1

RESET

Resets IOC or inverse time overload fault

SW2

BURDEN

SELECT

Calibrates current for nameplate rating of motor
Refer to current table on starter or Section 4.5.3.

3.4 TERMINALS

3.4.1 CUSTOMER TERMINALS

TERMINAL

NO.

DESCRIPTION

TB

1

115 VAC supplied to this input will enable the unit
to run

2

Common Fault relay contact. The relay is energized
when a fault exists

3

Normally open Fault relay contact

4

Normally closed Fault relay contact

5

115 VAC supplied for control logic

6,7

Dry run contact for external use or sealing contact for
start pushbutton with three wire control

AC

AC1, N

115 VAC control voltage input
AC1, N AC1 input is protected with internal fuse, 3A
250 VAC

TB1

RESET

A contact closure across these terminals will reset
any faults that exist.
For local panel door use, low voltage control.