2 link selection, 3 pushbutton and switches, 4 terminals – SAF OPAL SS6 User Manual
Page 21: 1 customer terminals, Link selection, Pushbutton and switches, Terminals, Customer terminals

OPAL SS6 Reduced Voltage Starters
Page 14
3.3.2 LINK SELECTION
LINK
NAME
POSITION
DESCRIPTION
JP1
DUTY
NO
JUMPER
With no jumper present, heavy duty mode
selected
Shipped from factory with no jumper
JP3
RATE
OFF
Selects constant current mode
RV1 has no bearing
ON
This selects current ramp mode which is
dependent on RV1
*Note : JP2 does not exist on this version
3.3.3 PUSHBUTTON AND SWITCHES
SWITCH
NAME
DESCRIPTION
SW1
RESET
Resets IOC or inverse time overload fault
SW2
BURDEN
SELECT
Calibrates current for nameplate rating of motor
Refer to current table on starter or Section 4.5.3.
3.4 TERMINALS
3.4.1 CUSTOMER TERMINALS
TERMINAL
NO.
DESCRIPTION
TB
1
115 VAC supplied to this input will enable the unit
to run
2
Common Fault relay contact. The relay is energized
when a fault exists
3
Normally open Fault relay contact
4
Normally closed Fault relay contact
5
115 VAC supplied for control logic
6,7
Dry run contact for external use or sealing contact for
start pushbutton with three wire control
AC
AC1, N
115 VAC control voltage input
AC1, N AC1 input is protected with internal fuse, 3A
250 VAC
TB1
RESET
A contact closure across these terminals will reset
any faults that exist.
For local panel door use, low voltage control.