OPAL SS6 Reduced Voltage Starters

Page 6

2.0 SPECIFICATIONS

2.1 POWER RATING

POWER

3ø, 200-600VAC, 50/60 Hz

CONTROL

115 VAC@50 Hz or 120 VAC@60 Hz, 12VA (fans are extra)

RATING

See Section 2.2
All models have 1600V PIV SCR's

CONTACTS

Run and fault relay contacts rated at 0.2A, 115VAC

PROTECTION

Short circuit by HRC fuses or circuit breaker (supplied upon request)

Voltage surge protection by MOV's across the SCR's

2.2 MAXIMUM RATINGS

OPAL

MODEL

HORESEPOWER

230V

460V

575V

SS6-15

5

10

15

SS6-30

10

25

30

SS6-50

20

40

50

SS6-80

30

60

75

SS6-125

50

100

125

SS6-200

75

150

200

SS6-360

150

300

350

SS6-500

200

400

500

SS6-600

250

500

600

SS6-800

300

600

800

2.3 SERVICE CONDITIONS

ELEVATION

For altitudes in excess of 2000 meters / 6600 feet above sea level, all

assemblies must be derated 1% for every 100 meters / 330 feet above

AMBIENT

Do not install in areas where ambient temperature falls below

TEMPERATURE 0°C / 32°F or exceeds 40 °C / 104°F