0 specifications, 1 power rating, 2 maximum ratings – SAF OPAL SS6 User Manual
Page 13: 3 service conditions, Specifications, Power rating, Maximum ratings, Service conditions

OPAL SS6 Reduced Voltage Starters
Page 6
2.0 SPECIFICATIONS
2.1 POWER RATING
POWER
3ø, 200-600VAC, 50/60 Hz
CONTROL
115 VAC@50 Hz or 120 VAC@60 Hz, 12VA (fans are extra)
RATING
See Section 2.2
All models have 1600V PIV SCR's
CONTACTS
Run and fault relay contacts rated at 0.2A, 115VAC
PROTECTION
Short circuit by HRC fuses or circuit breaker (supplied upon request)
Voltage surge protection by MOV's across the SCR's
2.2 MAXIMUM RATINGS
OPAL
MODEL
HORESEPOWER
230V
460V
575V
SS6-15
5
10
15
SS6-30
10
25
30
SS6-50
20
40
50
SS6-80
30
60
75
SS6-125
50
100
125
SS6-200
75
150
200
SS6-360
150
300
350
SS6-500
200
400
500
SS6-600
250
500
600
SS6-800
300
600
800
2.3 SERVICE CONDITIONS
ELEVATION
For altitudes in excess of 2000 meters / 6600 feet above sea level, all
assemblies must be derated 1% for every 100 meters / 330 feet above
AMBIENT
Do not install in areas where ambient temperature falls below
TEMPERATURE 0°C / 32°F or exceeds 40 °C / 104°F