The following table details the parameter configurations to meet Grade 3 requirements

in the UK:

Item

Grade 2

Grade

3

Explanation

USER CODES

4 digits

6 digits

NOTE: changing the number of code digits will require re-
defining all current user codes.

ANTI CODE
RESET

4 digits

6 digits

EVENT LOG

250
events

500
events

LightSYS2 always supports 512 events

ENGINEER
TAMPER

Not
required Required

For Grade-3, the system control bit “ENGR. TAMPER” shall
be defined as YES.

Menu = [Programming][System][Controls][Advanced]

YES: A Tamper event causes a Lockout condition which can

only be reset by the Engineer code or by Anti-Code.

NO: A Tamper event does not cause a Lockout condition

FAULT RESET

Not
required

Required

For Grade 3, the system control bit “Rest Fault” shall be
defined as YES.

Menu = [Programming][System][Controls][EN50131]

YES: A System Fault condition must be acknowledged by

the user

NO: A System Fault condition will reset automatically

when clear

DETECTOR
MASK AND
FAULT

Not
required

Required

For Grade 3, triple end-of-line termination is supported to
identify detector masking and fault. (fault for all Grades).

INHIBIT KEYPAD Not

required

Required

For Grade 3, 10 invalid code entry attempts will lock the
keypad for 90 seconds (relevant for all user codes and
operations – arming, disarming, etc.)

DUAL PATH
SETTING
PREVENTION

Required Required

If there is a communication fault with the ARC (by PSTN,
TCP/IP, GSM, or STU) the panel will not be ready to arm.