16 - SAFETY DEVICES AND ALARMS

WRITTEN ON THE

DISPLAY

TYPE OF PROBLEM

SOLUTION

A08

FLUE GAS FAN

Faulty smoke fan.

Check that the lower compartment is clean (see the

pages dedicated to stove cleaning) and verify that it is not

obstructed; clean it and cancel the alarm.

If the alarm persists, contact the service centre.

A09

SMOKE TEMPERA-

TURE PROBE

Smoke sensor fault.

Contact an authorised service centre to have the component

checked and, if needed, replace the component.

A11

GEAR REDUCER

Feed screw gear reducer fault.

The component is not working regularly.

Contact an authorised service centre to have the component

checked and, if needed, replace the component.

A13

BOARD TEMP

Electronic board overheating

Wait for the cooling phase to end, cancel the alarm and

reduce pellet loading (SETTINGS MENU - Pellet recipe). If the

alarm persists, contact the service centre. .

A14

ACTIVE SENSOR

Active sensor anomaly

Active Plus sensor operation anomaly. Contact an authorised

service centre to have the component checked and, if needed,

replace the component.

A18

WATER SIC

Water thermostat intervention

Water temperature is too high or thermostat operation

anomaly. If the alarm persists, contact the service centre.

A19

WATER PROBE

Fault with water sensor.

Possible fault in the safety component. Contact an authorised

service centre to have the component checked and, if needed,

replace the component.

A20

AUX PROBE

Auxiliary probe fault

Possible component fault.

Check that the probe inserted in the system respects the

characteristics specified in the instructions (see external

probe).

Contact an authorised service centre to have the component

checked and, if needed, replace the component.

Exiting the alarm conditions

NEVER open the appliance door whilst the stove is either in the initial startup or on its shut down cycle, pellets will

still be smoldering or therefore volatiles may be present.

ATTENTION!

If during operation or initial ignition you encounter smoke spillage in to the room from the appliance or the flue