beautypg.com

0 communications, 1 communications interface port, Table 2 db-9 pin assignment – Emerson Liebert GXT2-10000RT208 User Manual

Page 38: 1 db-9 interface port, Ommunications, Communications interface port, Table 2, Db-9 pin assignment

background image

Communications

32

11.0 C

OMMUNICATIONS

11.1 Communications Interface Port

The Liebert GXT2-10000RT208 UPS has a standard DB-9 serial port female connector located on the

rear of the UPS unit. Several signals are provided on this port and are assigned as follows:

11.1.1 DB-9 Interface Port

Using the following directions to attach the smaller enclosed ferrite

bead clamp to the communication cable as shown at right:
1. Open the ferrite bead.
2. Place the communication cable inside the ferrite bead groove.
3. Position the ferrite bead as close as possible to the end of the cable

that connects to the DB-9 connector of the UPS.

4. Close the ferrite bead so that the ferrite bead’s case snaps closed

with the cable routed through the ferrite bead’s case.

Table 2

DB-9 pin assignment

DB-9

Pin

Assignment Description

1

Low Battery (open collector)

2

UPS TxD (typical RS-232 levels)

3

UPS RxD (typical RS-232 levels)

4

Remote Shutdown (5-12VDC, 10-24mA max; battery operation)

5

Common

6

Remote Shutdown (short to pin 5); all modes of operation

7

Low Battery (open emitter)

8

Utility Fail (open emitter)

9

Utility Fail (open collector)

Pin Assignment

Collector to Emitter*

* Maximum voltage and current on pins 1, 7, 8 and 9 are 60VDC and 10.0 mA

5

4

3

2

1

6

7

8

9

(-)

(+)

330 Ohms

Open
Collector

Open
Emitter

Run cable

through ferrite