Configuration Program

23

8.5.4 On-Screen Reminders

As pending changes are selected, on-screen

messages will remind the user if the UPS may

be On, or must be Off, for the setting to be pro-

grammed once the Apply or OK button is

pressed. If there are no changes, these mes-

sages are shaded.
Values displayed will only be transmitted to

the UPS when either the Apply or OK button is

selected. The APPLY button sends the new set-

tings to the UPS without closing the program. The OK button sends the new settings and closes the

program.
Whenever data is successfully transmitted to the

UPS, this message will be displayed. If the UPS is

already ON, you do not need to restart it.

8.5.5 Programming Rejected When UPS is Off

If the UPS appears to be Off but this error message

is displayed when the APPLY Or OK button is

selected to transmit new settings on the UPS tab or

Options Tab, the UPS may be in an intermediate,

standby condition.
To Confirm That the UPS is Off, Repeat the Turn-Off Procedure
While the UPS is in Normal Mode operation, press the Off button once to put the UPS into Bypass

Mode. Once the UPS is in Bypass Mode operation, press and release the Off button two distinct times

(for about a second each time) to turn off the UPS.

Partial Rejection

If the UPS is not OFF and changes from both the Battery Tab and the (UPS Tab or Options Tab) are

selected, the UPS will only program the changes on the Battery Tab.