beautypg.com

C-11499 instruction cara owner's manual5, Trouble shooting – Enviro Cara User Manual

Page 39

background image

39

Trouble Shooting

Problem

Possible Cause

Solution

The main burner does not

ignite when called for.

The gas valve may not be on.

• Check that the gas control knob is in the “ON” position.

Thermostat is not calling for

heat.

• Adjust the thermostat several degrees above ambient

temperature.

Problem with gas valve.

• Use a DC voltmeter to measure the voltage across the

TPTH and TP terminals. Main operator voltage: Open

circuit ≥ 325mV Closed circuit ≥ 100mV

• If voltage is not present, check the control circuit for

proper operation.

• If proper control system voltage is present, replace the

gas control.

Spark will not light the pilot

after repeatedly pressing the

spark ignitor.

Defective piezo ignitor.

• Check connections to ignitor.

• If ignitor connections are good but no spark, replace

ignitor.

Broken spark electrode.

• Check for broken ceramic insulation, replace electrode if

broken.

Misaligned spark electrode.

• If spark is not arcing from electrode to pilot, loosen the

screws on the pilot base adjust and tighten.

Pilot will not remain lit.

Problem with thermocouple

circuit.

• Check for proper connection of the thermocouple to the

rear of the valve. If loose, fully tighten.

• Check pilot for full flame impingement around

thermocouple. If flame is too small, check gas pressure,

adjust pilot rate screw, check pilot head for damage.

• Check thermocouple voltage at valve. It must be greater

than 5 mV. If low, replace thermocouple.

Air in gas line (pilot dies while

knob is depressed).

• Bleed line.

• Check gas line pressure.

• Contact dealer.

Burners will not remain lit.

Problem with thermopile

circuit.

• Check gas line pressure .

• Check for flame impingement on thermopile. If low, see

“Pilot will not remain lit”.

• Check thermopile for minimum of 300 mV when burner is

switched on.

• Check wiring to thermostat for breaks.

Flame lifting

Leak in vent pipe

• Check for leaks in vent connections.

Improper vent configuration

• Check vent configuration with manual.

Terminal may be recirculating

flue gases

• Check to see if terminal is on correctly.

• May need to install high wind termination cap.

• Contact dealer.

Glass fogs up

Normal Condition: after the appliance warms up the glass will clear.

**Due to additives in gas, glass may get hazy during operation** Clean as needed.

Blue Flames

Normal during start up: flames will yellow as the fireplace heats up.

Flames are burning “dirty” or

sooting

Flame impingement

• Check log positioning.

• Increase primary air by opening the venturi shutter and/

or by opening the vent restrictor.

See also “Burners will not remain lit.”

Remote control doesn’t work

Problem with the remote

• One or more of the batteries are dead. See remote

control instructions.

Problem with fireplace

• The on/off switch is turned to OFF.

• The gas control valve is turned to PILOT or OFF.

• The pilot has gone out.