Initial installation – Enviro Cara User Manual
Page 16
When planning your installation, it will be necessary to select the proper length of vent pipe for your
particular requirements. It is important to note when passing through a wall, the maximum allowable
wall thickness is 10 inches (25.4 cm); 1½ inches (3.8 cm) clearance to combustibles must be maintained.
Select the amount of vertical rise desired for “vertical-to-horizontal” type installations. To determine
the length of vent pipe required for vertical installations, measure the distance from the appliance flue
outlet to the ceiling, the ceiling thickness, the vertical rise through the attic or second story, and allow
for sufficient vent height above the roof line. For two story applications, a fire stop is required at each
floor level. If an offset is needed in the attic, additional pipe and elbows will be required. To connect the
venting system to the appliance flue outlet, a twist-lock adapter is built into the appliance at the factory.
Refer to i
nitiaL
i
nstaLLation
- v
ent
c
onfiguration
and
r
estrictor
s
ettings
for venting parameters.
Your total vent pipe length must be within the grid area of Figures 28 and 29. If a 90° elbow is used in
the horizontal plane, 36” (91.4 cm) must be subtracted from the allowable horizontal run.
There are three (3) basic types of Direct Vent System installations. The three (3) types of installations are
shown in Figures 24 through 26.
a
PPRoveD
v
ent
P
aRts
:
Table 5: Approved Vent Manufacturers.
Manufacturer
Trade Name
Nominal Sizes
American Metal Products
AmeriVent Direct
4” - 6 5/8”
Security Chimneys International LTD
Secure Vent
4” - 6 5/8”
Selkirk Metalbestos
Direct-Temp
4” - 6 5/8”
Simpson Dura-Vent
Direct Vent GS
4” - 6 5/8”
The Cara fireplace has been tested and certified for use with AMERICAN METAL PRODUCTS “AMERIVENT
DIRECT”, SIMPSON DURAVENT TYPE GS PIPE FOR GAS STOVES. SECURITY CHIMNEY’S “SECURE VENT
DIRECT VENT SYSTEM” and SELKIRK “DIRECT-TEMP VENT SYSTEM” kits are available for horizontal and
vertical venting. When using Simpson Duravent, it is recommended that, before installation, a bead of
RTV High Temperature Silicone should be applied to each outer vent joint, and Mil-Pac to each inner
joint. When planning an installation, it will be necessary to select the proper length of vent pipe for the
particular requirements.
WARNING: Do not mix parts from different vent manufacturers’ systems.
EXCEPTION TO WARNING: This product has been evaluated by Intertek for using a Direct Vent GS
starting collar in conjunction with Secure Vent, Direct-Temp, and Ameri Vent Direct venting systems. Use
of these systems with the Direct Vent GS starting collar is deemed acceptable and does not affect the
Intertek WH listing of the appliance.
Initial Installation
QUALIFIED INSTALLERS ONLY
16