Eaton Electrical Powerware 5130 Rack/Tower UPS 1250-3000 VA User Manual
Page 50

ADDITIONAL UPS FEATURES
EATON Powerware
®
5130 Rack/Tower UPS (1250–3000 VA) User’s Guide
S 164201730 Rev 2
www.powerware.com
44
Table 6. Voltage Threshold Options (continued)
PW5130G3000-XL2U Function
Factory Setting
Other Available Settings
High threshold for transfer to battery
263 Vac
—
Low threshold for transfer to battery
160 Vac
—
Fader activation threshold
229 Vac
—
Booster activation threshold
177 Vac
—
Maximum input-voltage range
Disabled
Enabled
2
2
Low threshold for transfer to battery is 150V.
Table 7. UPS Sensitivity Options
Function
Factory Setting
Other Available Settings
UPS-sensitivity level
Normal
High or low
Table 8. UPS On/Off Options
Function
Factory Setting
Other Available Settings
Automatic start
Enabled
Disabled
Cold start
Enabled
Disabled
Forced shutdown
Enabled
Disabled
Energy-savings mode
Disabled
Enabled
UPS ON/OFF controlled by software
Enabled
Disabled
Battery level before restart
0%
0–100%
Table 9. Battery Options
Function
Factory Setting
Other Available Settings
Battery-test intervals
Weekly
No test / daily test / monthly test
Low-battery warning
20%
0–100%
Battery protection against deep discharge
Enabled
Disabled
Audio alarm
Enabled
Disabled
Additional battery module
Automatic detection of number of
battery modules
For specific batteries, 25–81 Ah