13

2.0 Installation

Figure 2-5, DC Cable to Inverter’s DC Terminals

DC cable

with ring lug

Inverter’s DC

+ terminal

M6-1.0 Hex nut

CAUTION:

Ensure nothing is placed

between the DC terminal

and the ring lug.

CSW1012

Inverter

Lock washer

#12 Flat washer

BATTERY

DC cable

with ring lug

bolt

flat washer

nut

lock washer

battery

post

battery terminal

Verify that the

DC cable lugs are flush

with the battery terminals.

Figure 2-4, DC Cable to Battery Terminals

ring terminal that accommodates a #8 screw, and is UL/CSA approved.

Recommended tightening torque is 20 lbf-in (2.3 N-m).

CAUTION: Ensure the total cable distance from the inverter to

the battery is within the requirement of Section 2.4.1 (DC Wire

Sizing).

9. Once the entire installation is complete, and all connections are verifi ed,

close the fuse disconnect (or circuit breaker) to provide power to the

inverter.