Magnum Energy CSW1012 User Manual
Page 17

© 2013 Magnum Energy, Inc.
13
2.0 Installation
Figure 2-5, DC Cable to Inverter’s DC Terminals
DC cable
with ring lug
Inverter’s DC
+ terminal
M6-1.0 Hex nut
CAUTION:
Ensure nothing is placed
between the DC terminal
and the ring lug.
CSW1012
Inverter
Lock washer
#12 Flat washer
BATTERY
DC cable
with ring lug
bolt
flat washer
nut
lock washer
battery
post
battery terminal
Verify that the
DC cable lugs are flush
with the battery terminals.
Figure 2-4, DC Cable to Battery Terminals
ring terminal that accommodates a #8 screw, and is UL/CSA approved.
Recommended tightening torque is 20 lbf-in (2.3 N-m).
CAUTION: Ensure the total cable distance from the inverter to
the battery is within the requirement of Section 2.4.1 (DC Wire
Sizing).
9. Once the entire installation is complete, and all connections are verifi ed,
close the fuse disconnect (or circuit breaker) to provide power to the
inverter.