beautypg.com

0 installation – Magnum Energy CSW1012 User Manual

Page 13

background image

© 2013 Magnum Energy, Inc.

9

2.0 Installation

Crimped and sealed copper ring terminal lugs with at least a 6mm (1/4”)

bolt hole to connect the DC wires to the inverter’s DC terminals.

The battery bank voltage MUST be between 10.5-15.5 for the inverter

to operate. If the voltage exceeds 16.0V, the inverter may be damaged.

To ensure the maximum performance from the inverter, all connections

from the battery bank to the inverter should be minimized. The

exceptions are the DC fuse and disconnect or the DC circuit breaker—

required at the battery to protect the DC wiring—in the positive line. Any

other additional connection will contribute to additional voltage drops,

and these extra connection points may loosen during use.

All wiring to the battery terminals should be checked periodically (once

a month) for proper tightness. The torque requirement for the DC

terminals is between 79 to 96 lbf-in (8.9 to 10.9 N-m). If you don’t have

a torque wrench, ensure all DC terminals are tight.

• Be aware that overtightening or misthreading the nuts on the DC

terminals can cause the bolts to strip and snap/break off.

Make sure cables have a smooth bend radius and do not become kinked.

Follow existing wire runs where possible.

A brief spark or arc may occur when connecting the battery cables to the

inverter DC terminals; this is normal and due to the inverter’s internal

capacitors being charged.

• Before routing the wiring, color code the DC cables/wires with colored

tape or heat shrink tubing: RED for positive (+); WHITE for negative (–);

and GREEN (or bare copper) for DC ground, to avoid polarity problems.

• Do not attempt to use the chassis in place of the battery negative

connection for grounding. The inverter requires a reliable return path

directly to the battery.

2.4.1 DC Wire Sizing

It is important to use the correct sized DC wire to achieve maximum effi ciency

from the system and to reduce fi re hazards associated with overheating.

Always keep your wire runs as short as practical to prevent low voltage

shutdowns and to keep the DC breaker from nuisance tripping (or open

fuses) because of increased current draw. The correct minimum DC wire

size (and corresponding overcurrent device) is required in order to reduce

stress on the inverter, minimize voltage drops, increase system effi ciency,

and ensure the inverter’s ability to surge heavy loads.
If the distance from the inverter to the battery bank is ≤5 feet, use a minimum

DC wire size of #2 AWG (33.6 mm

2

). If the distance between the inverter

and the battery is >5 feet, the DC wire will need to be increased. Longer

distances cause an increase in resistance, which affects the performance of

the inverter. From 5-10 feet, use a minimum wire size of #1/0 AWG (53.5

mm

2

)

wire; from 10-15 feet, use a minimum wire size of #2/0 AWG (67.4

mm

2

) wire.

Table 2-1, DC Wire/Overcurrent Device for Rated Use

Inverter

Model

Minimum DC Wire

Size [rating]*

Maximum DC

Fuse Size

DC Grounding

Wire Size*

CSW1012

#2 AWG (33.6 mm

2

)

[170 amps]

150 amps

with time delay

#2 AWG

(33.6 mm

2

)

* Copper wire rated with 75°C (167°F) insulation at an ambient temperature

of 30°C (86°F) in free air.