beautypg.com

Gpd 515g5 modbus register data – Yaskawa GPD 506/P5 Section Three User Manual

Page 44

background image

PP.P5G5.03.Troubleshoot

Page 44

Rev. 06/11/2003

GPD 515G5 MODBUS Register Data

The present fault may be obtained by accessing register 0090H. An
example of an OL1 fault being read from a GPD515/G5 with the
station address of 02 is shown below.

PLC

GPD

515/G5

02 03 0090 0001 84 14

Station
Address
(H5-01)

Read

Register

Command

Fault

Code

Register

CRC

High

CRC

Low

Length of

(# of Register)

TRANSMIT

RECEIVE

02 03 02 000B BD 83

Station
Address
(H5-01)

Register
Requested

# of
Bytes

Fault
(OL1)

CRC

High

CRC

Low

This manual is related to the following products: