PP.P5G5.03.Troubleshoot

Page 4

Rev. 06/11/2003

506

515

505

Undervoltage of the main circuit when running.
230V Units - trip point 190V DC or less.
460V Units - trip point 380V DC or less.
600V Units - trip point 546V DC or less.

UV1

DC Bus Undervolt

U

u

1

Undervoltage of the control circuit when running.
230V Units - 30kW ~ 75kW, monitors the (-15V)

power supply.
460V Units - 55kW ~ 160kW, monitors the (-15V)

power supply.

UV2

CTL PS Undervolt

U

u

2

Possible Cause(s):

Single phase condition on the input, low input voltage at L1, L2, and L3.

Corrective Action:

Check the three phase input voltage, verify L2-05 for 515/G5 units.

Possible Cause(s):

External load connected pulling down the inverter power supplies.

Corrective Action:

Repair or replace the power/gate drive board.

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.