o

h3

Inverter overheat pre-alarm signal is input from the

multi-function input terminals.

OH2

Over Heat 2

The transistor cooling fin temperature exceeded the
allowable value. GPD 506/P5 (95 ° C),
GPD515/G5 (95 ° C) Response may be selected.

o

h1

N/A ?

OH

Heatsnk Ovrtemp

Possible Cause(s):

Cooling fan(s) are not working, high ambient temperature.

Corrective Action:

Check for dirt build-up on the fans, reduce the ambient temperature

around the inverter.

Possible Cause(s):

An external overheat condition exists connected to one of the multi-

function input terminals 3, 4, 5, 6, 7, or 8.

Corrective Action:

Check for an external condition, verify the program parameters.

Fault Codes

Minor Fault

- Operation continues and the digital operator indication blinks

The fault relay does not activate.