beautypg.com

Fault codes, Major fault – Yaskawa GPD 506/P5 Section Three User Manual

Page 12

background image

PP.P5G5.03.Troubleshoot

Page 12

Rev. 06/11/2003

The braking transistor has failed.
230V Units - 0.4kW ~ 7.5kW
460V Units - 0.4kW ~ 15kW

RR

DynBrk Transistr

The braking resistor temperature has exceeded the

allowable value.
(Protects Yaskawa 3% duty cycle resistors only)

Can be selected as a minor fault by using the multi-
function outputs.

RH

DynBrk Resistor

Possible Cause(s):

Shorted braking transistor, high DC bus voltage, defective braking

resistor.

Corrective Action:

Replace defective transistor or resistor, monitor DC bus level.

Possible Cause(s):

Overhauling load, extended braking duty cycle, defective braking

resistor.

Corrective Action:

Verify braking duty cycle, monitor DC bus voltage, replace resistor.

505

N/A

N/A

Fault Codes

Major Fault

- Motor coasts to a stop, the fault is displayed on the digital

operator, and the fault relay is activated.

506

515