beautypg.com

Yaskawa F7 Drive Overvoltage Suppression User Manual

Page 5

background image

Date: 09/17/2010, Rev: 09-2010

Page 5 of 9

TM.F7SW.062

4.3 Monitors (U1-XX)

Monitor Num

ber

Modbu

s Add

ress

Monitor Name

Digital Operator

Display

Description

Scaling for Multi-

function Analog

Output

(H4-01/H4-04)

Unit

A

cce
ss

Le
vel
*1

U1-90 0720H

Soft Start Frequency

Reference

Soft Start Freq

Displays the
frequency reference
after the soft starter,
but before the OV
Regulator PI
controller output.

100% =

Fmax (E1-04)

0.01

Hz

Q

U1-91 0721H

Overvoltage Frequency

Reference

OV Reg Total Ref

Displays the
frequency reference
after the output of the
OV Regulator PI
controller.

100% =

Fmax (E1-04)

0.01

Hz

Q

U1-92 0722H

Overvoltage

Suppression Regulator

Error Signal

OV Reg Error

Displays the error
(setpoint - feedback)
of the OV Regulator
PI controller.

100% =

Motor Rated

Torque (Iq)

0.1

%

Q

U1-93 0723H

Overvoltage

Suppression Regulator

Output

OV Reg Output

Displays the output of
the OV Regulator PI
controller.

100% =

Fmax (E1-04)

0.1

%

Q

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”. V/F and Open Loop Vector only.

4.4 Faults

Fault Display

Description

Cause

Countermeasures

B-BRK

Belt Break

The drive’s output
frequency was at the
maximum output
frequency (E1-04) for
more than 30 seconds.
See section 6.3 for details.

Fix belt / coupling.


4.5 Alarms

Alarm Display

Description

Cause

Countermeasures

OTDLY

Overtemp Delay

Over-temperature Delay

The drive’s heat sink
temperature exceeded
parameter L8-02
(Overheat Pre-alarm
Level) and then fell below
the L8-02 level within the
P2-01 time. This alarm will
flash until the P2-01 timer
has expired. See section
6.4 for details.

Decrease the drive heat

sink temperature. Check

the drive’s cooling fans.

Check the sizing of the

drive’s enclosure.