Yaskawa F7 Drive Overvoltage Suppression User Manual

Page 4

background image

Date: 09/17/2010, Rev: 09-2010

Page 4 of 9

TM.F7SW.062

4.2 Pumpjack Application Specific Parameters

Paramete

r

Numb

er

Modbu

s

Addre

ss

Parameter Name

Digital Operator

Display

Description

R

ang

e

Default

Cha

nge

Duri

ng Run

Access Level *1

P1-07 0606H

OV Regulator Gain

Frequency

Gain Frequency

*2

This parameter sets the OV
regulator gain change endpoint.
See section 5.3 for details on this
function.

0.00 ~

400.00

Hz

90.0

0

Yes A

P1-08 0607H

OV Regulator Gain

Multiplier

Gain Multiplier

*2

This parameter sets gain multiplier
for the OV regulator gain (P1-02)
based on output frequency. See
section 5.3 for details on this
function.

1.000 ~

10.000

1.30

0

Yes A

P2-01 060AH

Heatsink Overheat

Off -Delay Time

OH Off Delay

This parameter sets the amount of
time that the drive will revert to a
reduced speed after an Overheat
Pre-alarm occurs. See section 5.5
for details.

0.0 ~

30.0

min

0.0 No A

P2-02 060BH

Heatsink Overheat

Speed Reduction

OH Spd Reduce

This parameter sets the multiplier
used to reduce the frequency
reference after an Overheat Pre-
alarm occurs. See section 5.5 for
details.

Note: 100% = Fmax (E1-04)

0.0 ~

100.0

%

100.

0

No A

P2-03 060CH

Belt Break Detection

Belt Break Det.

This parameter configures the Belt
Break Detection function. If the
drive’s soft starter is at maximum
output frequency (E1-04) for more
than 30 seconds, a belt-break fault
(B-BRK) will occur. See section 5.4
for details.

0: Disabled
1: Enabled

0 ~ 1

1

No

A

P3-01 0614H

Torque Limit During

Start

Start Torque

This parameter determines the
forward and reverse motoring
torque limits after a run command
is received, but before the torque
start timer (P3-02) expires.
Overwrites L7-01 and L7-02.

0 ~ 300

%

200

%

No A

P3-02 0615H

Torque Limit During

Start Timer

Start Torq Time

This parameter sets the time that
parameter P3-01 will overwrite L7-
01 and L7-02 after a run command
is received.

0.0 ~

10.0

sec

0.0 No A

P3-03 0616H

Torque Limit During

Start Ramp Time

Torq Lim Ramp Tm

This parameter sets the time
required to ramp the torque limit
100%. This determines the rate at
which the torque limits will return to
the L7-01 and L7-02 values at the
end of the starting torque time (P3-
02).

0.1 ~

10.0

sec

1.0 No A

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”. V/F and Open Loop Vector only.
*2: Making large changes in these settings while the drive is running can result in large and very rapid changes in
the output frequency. Change these parameters in small increments only.