3.0 Limitations

a. V/Hz and Open Loop Vector are the only control modes (A1-02 = 0 or 2) that support the Overvoltage

Suppression function. Closed Loop V/F and Closed Loop Vector are available (A1-02 = 1 or 3) but the
Overvoltage Suppression function is disabled.

b. Bi-directional Speed Search. For some applications, when motor loading is extremely light at startup, it

may be necessary to disable the bi-directional speed search feature by setting parameter B3-14 = 0.



4.0 Related Parameters and Functions

4.1 Overvoltage Suppression PI Controller Parameters

Paramete

r

Numb

er

Modbu

s

Addre

ss

Parameter Name

Digital Operator

Display

Description

R

ang

e

Default

Cha

nge

Duri

ng Run

Access Level *1

P1-01 0600H

OV Suppression PI

Setpoint

OV Reg Setpoint

*2

This parameter sets the OV
Suppression PI setpoint in
percent of motor torque-
producing current (Iq).

Note: 100% Iq = 100% motor
rated torque.

-100.0 ~

100.0

%

12.0 Yes A

P1-02 0601H

OV Suppression

Proportional Gain

OV Reg Gain

*2

This parameter sets the gain of
the OV Suppression PI
controller. This determines the
responsiveness of the Iq
regulator. A larger setting equals
more responsiveness.

0.00 ~

25.00

2.20 Yes A

P1-03 0602H

OV Suppression Integral

Time

OV Reg I Time

*2

This parameter sets the integral
time of the OV Suppression PI
controller. This determines the
responsiveness of the Iq
regulator. A smaller setting
equals more responsiveness.

0.00 ~

160.00

sec

0.10 Yes A

P1-04 0603H

OV Suppression Positive

Integral Limit

OV Reg I Limit

This parameter sets the positive
limit of the integrator in the OV
Suppression PI controller.

Note: 100% = Fmax (E1-04).

0.0 ~

100.0

%

100.0 No A

P1-05 0604H

OV Suppression Positive

Overall Limit

OV Reg Limit

This parameter sets the positive
limit of the OV Suppression PI
controller (P+I).

Note: 100% = Fmax (E1-04).

Note: A setting of 0.0% disables
the OV Suppression PI
controller.

0.0 ~

100.0

%

100.0 No A

P1-06 0605H

Motor Torque Producing

Current (Iq) Feedback

Filter Time

Feedback Filter

*2

This parameter sets the 1

st

order filter time of the motor
torque-producing current
feedback. A larger setting
equals a more filtered feedback
but less responsiveness.

5 ~

10000

msec

100 Yes A

*1: Access Level (A1-01): Q = “Quick Start”, A = “Advanced”, F = “Factory”. V/F and Open Loop Vector only.