Yaskawa America, Inc. –

www.yaskawa.com

IG.AFD.23.BACnet, Page 8 of 12

Date: 7/07/2011 Rev: 11-07

BACnet

®

Option

Installation Guide

AV7

Fault Details

0

Overcurrent

OC

Ground Fault

GF

Read

Bit Field

1

Over Voltage

OV

2

Drive Overload

OL2

3

Drive Overheat

OH1

Drive Overload

OH2

4

Breaking Transistor Fault

rr

Breaking Resistor Overheat

rH

5

Fuse Blown

PUF

6

PID Feedback Loss

FbL

7

External Fault

EF, EF3, EF4, EF5,
EF6, EF7

8

Hardware Fault

CPF

9

Motor Overload

OL1

Drive Overload

OL2

Overtorque

OL3

10

PG Disconnect

PGO

Overspeed

OS

Speed Deviation

DEV

11

Under Voltage Detect

UV

12

Main Circuit Undervoltage

UV1

Control Circuit Undervoltaqge UV2
MC Error

UV3

13

Output Phase Loss

SPO

Input Phase Loss

SPI

14

Drive Communication Error

CE

15

Operator Connection Error

OPR

AV8

Data Link Status

0

@ Writing Data

Read

Bit Field

1

Reserved

2

Reserved

3

@ Limit Fault

4

@ Data Compatibility Fault

5-15

Reserved

AV9

Frequency Reference

U1 – 01 Scaled by Parameter o1-03 with Units from Parameter
o1-09

Read

o1-03

o1-09

AV10

Output Frequency

U1 – 02 Scaled by Parameter o1-03 with Units from Parameter
o1-09

Read

b5-20

b5-31

AV11

Output Voltage

U1 – 06

Read

0.1

VAC

AV12

Output Current

U1 – 03 Scale Dependent on drive model
Models 0h ~ 6h and 20h ~ 27h are 0.01A
Models 7h ~ 1Fh and 28h ~ 3Fh are 0.1A

Read

A

AV13

Output Power

U1 - 08

Read

0.1

kW

AV14

Torque Reference

Not Supported in E7/P7

Read

0.1

%

AV15

MF Input Status

0

@ Terminal S1 Closed

Read

Bit Field

1

@ Terminal S2 Closed

2

@ Terminal S3 Closed

3

@ Terminal S4 Closed

4

@ Terminal S5 Closed

5

@ Terminal S6 Closed

6

@ Terminal S7 Closed

7

@ Terminal S8 Closed

8-15

Reserved

Obj ID

Obj Name

Bit

Name

Read/ Write

Scale

Unit