Bacnet, Option installation guide – Yaskawa BACnet Option User Manual
Page 8

Yaskawa America, Inc. –
IG.AFD.23.BACnet, Page 8 of 12
Date: 7/07/2011 Rev: 11-07
BACnet
®
Option
Installation Guide
AV7
Fault Details
0
Overcurrent
OC
Ground Fault
GF
Read
Bit Field
1
Over Voltage
OV
2
Drive Overload
OL2
3
Drive Overheat
OH1
Drive Overload
OH2
4
Breaking Transistor Fault
rr
Breaking Resistor Overheat
rH
5
Fuse Blown
PUF
6
PID Feedback Loss
FbL
7
External Fault
EF, EF3, EF4, EF5,
EF6, EF7
8
Hardware Fault
CPF
9
Motor Overload
OL1
Drive Overload
OL2
Overtorque
OL3
10
PG Disconnect
PGO
Overspeed
OS
Speed Deviation
DEV
11
Under Voltage Detect
UV
12
Main Circuit Undervoltage
UV1
Control Circuit Undervoltaqge UV2
MC Error
UV3
13
Output Phase Loss
SPO
Input Phase Loss
SPI
14
Drive Communication Error
CE
15
Operator Connection Error
OPR
AV8
Data Link Status
0
@ Writing Data
Read
Bit Field
1
Reserved
2
Reserved
3
@ Limit Fault
4
@ Data Compatibility Fault
5-15
Reserved
AV9
Frequency Reference
U1 – 01 Scaled by Parameter o1-03 with Units from Parameter
o1-09
Read
o1-03
o1-09
AV10
Output Frequency
U1 – 02 Scaled by Parameter o1-03 with Units from Parameter
o1-09
Read
b5-20
b5-31
AV11
Output Voltage
U1 – 06
Read
0.1
VAC
AV12
Output Current
U1 – 03 Scale Dependent on drive model
Models 0h ~ 6h and 20h ~ 27h are 0.01A
Models 7h ~ 1Fh and 28h ~ 3Fh are 0.1A
Read
A
AV13
Output Power
U1 - 08
Read
0.1
kW
AV14
Torque Reference
Not Supported in E7/P7
Read
0.1
%
AV15
MF Input Status
0
@ Terminal S1 Closed
Read
Bit Field
1
@ Terminal S2 Closed
2
@ Terminal S3 Closed
3
@ Terminal S4 Closed
4
@ Terminal S5 Closed
5
@ Terminal S6 Closed
6
@ Terminal S7 Closed
7
@ Terminal S8 Closed
8-15
Reserved
Obj ID
Obj Name
Bit
Name
Read/ Write
Scale
Unit